AbstractOBJECTIVE: To propose a standardized protocol for the evaluation of Legionella contamination in air.DESIGN: A bathroom having a Legionella contamination in water >1,000 cfu/l was selected in 10 different healthcare facilities. Air contamination was assessed by active (Surface Air System, SAS) and passive (Index of Microbial Air, IMA) sampling for 8 hours, about 1 m away from the floor and 50 cm from the tap water. Two hundred liters of air were sampled by SAS every 12 min, after flushing water for 2 min. The IMA value was calculated as the mean value of colony forming units/16 plates exposed during sampling (2 plates/hour). Water contamination was evaluated at T0, after 4 and 8 hours, according to the standard methods.RESULTS: Air contamination by Legionella was found in three healthcare facilities (one with active and two with passive sampling), showing a concomitant tap water contamination (median=40,000; range 1,100-43,000 cfu/l). The remaining seven hospitals isolated Legionella spp. exclusively from water samples (median=8,000; range 1,200-70,000 cfu/l).CONCLUSIONS: Our data suggest that environmental Legionella contamination cannot be assessed only through the air sampling, even in the presence of an important water contamination

Legionella spp. contamination in indoor air: preliminary results of an Italian multicenter study

TARDIVO, Stefano;
2014-01-01

Abstract

AbstractOBJECTIVE: To propose a standardized protocol for the evaluation of Legionella contamination in air.DESIGN: A bathroom having a Legionella contamination in water >1,000 cfu/l was selected in 10 different healthcare facilities. Air contamination was assessed by active (Surface Air System, SAS) and passive (Index of Microbial Air, IMA) sampling for 8 hours, about 1 m away from the floor and 50 cm from the tap water. Two hundred liters of air were sampled by SAS every 12 min, after flushing water for 2 min. The IMA value was calculated as the mean value of colony forming units/16 plates exposed during sampling (2 plates/hour). Water contamination was evaluated at T0, after 4 and 8 hours, according to the standard methods.RESULTS: Air contamination by Legionella was found in three healthcare facilities (one with active and two with passive sampling), showing a concomitant tap water contamination (median=40,000; range 1,100-43,000 cfu/l). The remaining seven hospitals isolated Legionella spp. exclusively from water samples (median=8,000; range 1,200-70,000 cfu/l).CONCLUSIONS: Our data suggest that environmental Legionella contamination cannot be assessed only through the air sampling, even in the presence of an important water contamination
2014
legionella spp; contamination; indoor air
File in questo prodotto:
File Dimensione Formato  
EP2014_I6S2_062.pdf

accesso aperto

Tipologia: Altro materiale allegato
Licenza: Dominio pubblico
Dimensione 101.08 kB
Formato Adobe PDF
101.08 kB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11562/906196
Citazioni
  • ???jsp.display-item.citation.pmc??? 7
  • Scopus 22
  • ???jsp.display-item.citation.isi??? ND
social impact